new bathroom fan in loft - no room at the eaves

Jun 09, 2024 Last reply: 2 years ago 32 Replies

Hi, DIYers



We're having the bathroom done, I wanted to install an inline fan in the loft and was planning to do the work ourselves to help the budget a bit. Thankfully this timely video

formatting link
surfaced which pretty much covers what I wanted to do.



The plan was/is to exit via the soffit. What the video doesn't show is actually getting the ducting out the eaves, I can only assume his was straight forward. Having got up there and found my exit point there is hardly any clearance and no way enough to push ducting through; if I did it would be squashed flat.



Pictures:

formatting link
At the top is the sarking, just about where the eaves begin is there's a batten above so no way to stretch that up. Then you can see a pad of mortar and the first row of bricks, the grey area is the bathroom ceiling. The wire is a PoE cable leading outside. The rafters are roughly 7.5cm but the notching at the wall means much less of a gap.



For some reason I thought I had more room and a clear row of bricks at the eaves so I originally thought I could chop out a brick and might have enough clearance. Aside from not wanting to disturb the rafters there is no headroom and I don't think I could have much control over tools (powered or otherwise) in that space. Don't want a brick falling out onto the soffit either.



I'm wondering if I still have any options to go that way?


The alternative would be to run the ducting to the gable end, I didn't favour this for a few reasons;



  • 2x longer run of ducting than soffit exit. I've bought flexible insulated duct but would prefer solid for that run
  • wanted to install the fan as close to the exhaust as possible for performance but if I do so it's harder to access for maintenance, needs longer cable run, it will be located above bedrooms rather than the bathroom itself in case of unwanted noise
  • The wall is SW facing and we have had issues with penetrating damp


New to newsgroups so apologies if I commit a faux-pas. I'll later have some related electrical questions; should I start a new post for those or continue this one?


Anything here (or from similar suppliers) worth considering:

formatting link

Many of the new builds round here seem to have two or three ventilated tiles in their roofs.

It's up to you. It could be best starting a new thread for your convenience if you want to keep it all under one obvious subject that you might want to refer to later. Anyway, the way threads drift off subject here and elsewhere means it probably won't matter in the long run!

Xan you transition to rectangular ducting for the exit, either rigid or flexible type?

formatting link

Andy Burns snipped-for-privacy@andyburns.uk wrote in news: snipped-for-privacy@mid.individual.net:

Or indeed super slim versions eg. 234x29:

formatting link
Yes, rigid but that may actually aid placement in the tight space concerned.

Plenty of useful adaptors/corners in the range.

For the o/p, short runs best to avoid condensation in the duct and dripping back or smelling.

fred snipped-for-privacy@for.mail wrote in news:spz9O.51303$y snipped-for-privacy@fx02.ams:

Worth shopping around for "225mm flat ducting", the Manrose version appears significantly cheaper from some sources:

formatting link

As it happens I came across a similar problem yesterday. What I thought was the back of the soffit was actually the inner skin of blocks, and there's then the cavity and outer brick skin. In my case there was insulation (and a bird's nest) in the gap so I could access the soffit, but need very long arms.

Looking at a diagram (of a soffit ventilated roof, but bear with me):

formatting link
it looks like your brick skin goes right up to the sarking, without leaving any kind of gap.

Have you thought about doing it from the outside? ie take the soffit off, drill whatever hole in the bricks you need to get access to the loft.

You could use rectangular ducting to get through this gap, perhaps adapting back to circular ducting:

formatting link
How much height do you have? From the picture it looks like about a brick, which isn't much, but I can't see what the grey thing in front of the brick is. I think the small rectangular duct is 110x54mm so that might just fit.

Looks fine to me. I'd start a separate thread as a new title it may attract those who know about electrics.

Theo

Squashing the ducting is the answer. The duct diameter is not altered hence the area enclosed though a different shape is the same, as long as you do not completely squash it flat. I did that with my inline fan and no problems it clears the vapour in the bathroom in a matter of minutes in fact by the time I am out of the shower and jumped into some clothes all glass panels and mirror are completely clear.

I'll get back later to all your questions and suggestions. Just wanted to exclaim that while it's fiddly to have to use the computer to reply it's already worth the effort to get this set up. So much better than a certain forum I will not ;-) be using again.

<snip>

Not the question that you asked, but have you considered putting a non- return flap in your ducting run? Our bathroom fan duct (in line fan) in the loft is waiting for one to be fitted, because there can be quite a strong draught back through the duct. OK in summer but can lower the bathroom temperature in winter by several degrees.

Cheers

Dave R

Christ in a bike, Some needs to go back to school

I think it's worth considering, yes. I've discounted it so far and it's my least favourite option as I assume the roof is original and don't really want to disturb things if I can help it. It will need doing at some point.

Thank you I'd seen rectangular solid duct but didn't know this flexible rectangular existed!

Wasn't sure if you were using the round insulated ducting as per the video, if it's important for noise reduction to keep to a similar ducting?

I've bought round insulated, swayed a little by the video - I know technically it's sound insulation but I suspect the foil ducting is louder than solid even with the insulation. I was hoping it would instead offer some element of thermal protection and then reduce the amount of condensation (hopefully better than nothing).

I didn't buy one but thanks for mentioning it, I'm keen to hear any real experiences. I'm not against it, wanted to see if it's an issue. Does yours vent through the soffit? I was thinking the wind blowing across the soffit would create more of a suction effect if anything - and cause knocking if it were blustery. Have you gone for a straight forward type with a round disk and offset pivot?

There's a certain faff factor that kicks in. The soffit panel in question is one long piece, possibly 4-5m. I don't think I could remove this from a ladder so I'd need a tower - I also suspect whoever put it up there, "did the job" with a view that when it comes down it'll be at the end of its life... so maybe it won't come cleanly.

However, I'm considering if, once I have a 4" hole in the soffit, I could get enough access through it to make the hole. Maybe?

Yes possibly a brick's worth, if the area visible were to be removed. The grey is the ceiling plasterboard. It goes almost all the way to the brick. Using an inspection mirror there is insulation beyond the edge. The white cable just visible in the centre is the 12v feed to the existing wall mounted extractor beneath. That wall has additional boxing and the fan duct goes through the lot to outside. I'll see if I can check if that cable is coming into the wall cavity or the boxing cavity.

A few mentions for rectangular ducting. I had seen it in the TLC catalogue and I'll have to look into it some more. Wasn't sure if I could make it fit either. And fiddly work as I'd have to probably go for a few in series Round-to-rectangle converter ==> 135 degree angle ==> rectangle-to-round ... connecting some of it from the loft and trying to fit the rest/ fiddle around with it all from the soffit side without it coming apart.

With any of the rectangle profiles I assume the adaptors and bends won't interface directly and need a joining piece so it adds up.

Thanks for highlighting the super slim ducting. This is interesting and looks worth further research. These thinner ones may well do it.

Sorry I'm still trying to work out how replying and quoting works, not sure how this is going to come out

In message <v47oqn$jmkb$ snipped-for-privacy@dont-email.me, Silent Ice snipped-for-privacy@example.null writes Snip

I suppose you could utilize the existing wall outlet if it is close to the ceiling. Round duct across the loft and re-enter near the wall...

Alternatively, cut a large enough hole in the soffit to work safely from your ladder. Cover with a rectangular sheet, pre-bored to suit the extractor outlet. You are only trying to keep Sparrows out:-)

>

I don't know if it is an option for you, but facing a similar problem, I dropped the vent pipe through the ceiling, into the airing cupboard and then through the wall lower down.

My cupboard goes up to the (suspended) ceiling, but if I'd not put that in and still just had the original ceiling above, I could have used a piece of enamelled steel tubing to bridge the gap, like you often see for a vent or boiler in a kitchen.

<snip>

The vent is directly above the bath, and goes up into the loft and out to the soffit via an in line fan and bendy tubes.

The flap is a standard one (we have them on the downstairs extractors) but I can't recall where it pivots.

Cheers

Dave R