I've been investigating an intermittent RCD trip on 120 meters of armoured cable supplying an electric gate. Was it ever acceptable to just lay it on the surface of the ground, albeit at the base of a wire fence in a field? I believe it was installed about 10 years ago. The outer plastic sheath has been gnawed (rabbits?) in numerous places over the entire length exposing the armour, surprisingly a megger test hasn't shown any problems, so investigation continues...
Peter