I'm routing projector cable through my plasterboard ceiling and down a wall. There are mains and AV cables. My simple question is, should I mount back boxes for the outlets on the joists in the same way that they would be mounted to a stud in a stud partition?
Antony
Didn't find your answer? Ask the community — no account required.
S
Sparks
That's what I would do if it were easy - otherwise, I would use a dry lining box like this
formatting link
A
antgel
Is this box supposed to screw into the _plasterboard_?
Antony
S
Sparks
Nope, the yellow bits at the side just clip in (they are springy)
Sparks...
A
antgel
Aha. That's great. Does it sit flush?
L
Lobster
Yep, near as damnit. You're going to set a 13A socket into the ceiling, though? I think(?) there's nothing against it regs-wise, but... eeew! Can't it go in the wall conventionally, just below the ceiling level? Or is the projector going to be suspended from the middle of the ceiling?
David
O
Owain
Preferably. There's quite a lot of force involved in pushing/pulling a good stiff 13A plug/socket.
If you have a selection of sockets to accommodate in the middle of the ceiling I'd suggest using a floorbox upside-down, as this may be neater than lining up several separate sockets, and less visually intrusive if painted to match the ceiling.
Owain
M
Mike Dodd
Off-topic all together, you might want to look at mounting the connectors all together on a single blanking plate. I routed Component video and mains to a single blanking plate and fitted an IEC mains socket and 3 phono sockets so that the PJ was fed from the single plate. Looks neat, but I'm sure someone will explain why I shouldn't have done it (reg's-wise). Lemme know if you'd like a photo to explain what I've done.
Out of interest... anyone familiar with regs... With the above description, even if there is something in the regs forbidding placing two or more services - e.g. video and mains - in the same box, what I've done is put two boxes in a stud-partitioned wall, one at 2M (PJ height), one just above skirting; the low one has mains "plug" type fitting, fed from a 13A mains lead plugged into standard 13A socket (all behind the settee), with wiring up to the high one, where theres the mains socket that the PJ plugs into. Does this constitute a fixed installation (there's no services here, since the supply and the video all plug into the lower plate) - all there are are two sockets/plates and wiring between the two plates, and would it be subject to any regulations?
Mike
A
antgel
Indeed, it's being suspended from the middle of the ceiling. Well, not quite the middle as the bracket needs to screw into a joist. :) These dry lining boxes will be just the ticket.
Although I think I've just decided to mount normal back boxes in the concrete above the plasterboard ceiling. I have a 35mm gap, which is perfect, and that's something that I know that I can do. :)
Antony
M
Mike
That's fine. But best practice is to use a non-fused type of connector (e.g. IEC or old 15A roundpin) with a fused FCU controlling the spur at an accessable height.
F
Frank Erskine
Very true, and is normal theatre practice, but normally the only time a fuse blows is when the "bulb" fails, so you have to climb up there anyway :-)
M
Mike
Yep. And once upon a long time ago I used to climb up there regularly. But at least with no fuse up there you only had a single point of failure.
Join the Discussion
Have something to add? Share your thoughts — no account required.
Didn't find your answer?
Ask the community — no account required
Report Content
You are reporting this content to the moderators. They will look at it
ASAP.