Romex to flex cable junction?

Jan 28, 2006 3 Replies

Hello all, I have to drop a line from the ceiling to a furnace. Currently its romex along the ceiling, with more to spare hanging down, and I need to come down in flex cable. So I bought some empty shell flex jacket.



I was going to thread the romex into the empty flex, and at this top "junction" use a metal box to clamp the jacket, even though the romex is not actually cut.



This sound ok?



Thanks



Dean



That will be fine, use a plastic threaded bushing on the threaded end of the greenfield connector. Staple the Romex to the framing within a foot of the greenfield and put a strap or 2 on the greenfield so everything stays put. The 2005 code is cleaning up the language to make this better defined as OK.

Hmm, thanks for that. Didn't think of such a thing. Got them in HD/Lowes?

Cheers,

Dean