how to carry out a dynamic water pressure test
-------------------------------------
##-----------------------------------------------## Delivered via http://www.thestuccocompany.com/ Building Construction and Maintenance Forum Web and RSS access to your favorite newsgroup - alt.building.construction - 15536 messages and counting! ##-----------------------------------------------##
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload

On the end of the pipe fit a pressure guage and a full bore valve. Adjust the valve until you achieve the required flow rate in L/Min. Record the pressure.
You could actually plot a graph of flow rate vs pressure....
With zero flow (eg valve closed ) you are measuring the static pressure. With valve fully open you will measure close to the "zero" pressure maximium flow rate. Plot several points in between.