How do I identify the high pressure switch and how does one bypass it?
Here's what I've found so far. The spade connector contacts on both the capacitors were highly corroded. I used a Dremel to grind off rust to get a clean contact surface.
The electromagnetic contact switch works, definitely engages. I hooked everything back up, put the top of the unit back on secured it with a few of the screws.
The top fan works so apparently that capacitor isn't bad enough to prevent that. As I was sitting by the unit after a few minutes I heard a humming noise that sounded like the compressor had momentarily kicked in but then stopped.
Further, on that circuit board there's a red LED that flashes while the unit is running.
Here's what I've found so far. The spade connector contacts on both the capacitors were highly corroded. I used a Dremel to grind off rust to get a clean contact surface.
The electromagnetic contact switch works, definitely engages. I hooked everything back up, put the top of the unit back on secured it with a few of the screws.
The top fan works so apparently that capacitor isn't bad enough to prevent that. As I was sitting by the unit after a few minutes I heard a humming noise that sounded like the compressor had momentarily kicked in but then stopped.
Further, on that circuit board there's a red LED that flashes while the unit is running.
Maybe if you were to take a crowbar to your wallet and called a *competent*, licensed, insured, professionally trained tech??
I may end up eventually doing that, but apparently it bothers you that I'd like to learn something about the workings of the unit and be somewhat informed and would also like to see if I get lucky and solve the problem with the replacement of a relatively inexpensive part or two.
Of course another issue is, in the Yellow Pages, they don't make a clear distinction between "Honest, fairly priced genuinely competent tech" and "bungling, meth-addict ripoff artist".
On May 4, 7:35=A0am, "Stormin Mormon"
I'll e-mail the cash to you.
Thanks. Just printed it out.
Replaced both the fan cap and compressor cap and it's runnin' like a champ now. The guy at the parts place put a meter on them and said the fan cap was on its way out and the compressor cap was kaput. The shape on the compressor cap is different - this one is oval, the old one was cylindrical about like an old car coil. However the ratings are the same and it appears to work.
Apparently it doesn't matter which side the connectors get attached to? I.e. there's not a "pos" and "neg"? It seems to be running fine.
One thing that makes me curious - I noticed that even with both the breaker for the A/C compressor on the main panel and the exterior breaker at the compressor turned off, when I turned on the air handler, the compressor relay switch still activated. I thought if the breakers are off, it interrupted the circuit to the compressor and nothing should get to any part of the unit?
Thanks again.
Yeah, but he will send in by Mormon mail and it will cost another $50. Those mules are real slow too.
>
I will email the capacitor right away.
$5 won't even buy a decent cup of Starbucks. Union rates indicate a minimum of $120.00
And a wind blowing over a block of ice.
Lets just say that the Contractors Association got a wind of that and 92 contractors blackballed the vendor. Who would you rather have as a customer? 92 Contractors that each purchase from $50k to $500K and more per year or some dipstick that purchases a $15 dollar item once every 10 years. Also many Vendors require Contractors to guarantee so much $$$$ business per year to cover price fluxuations and amount of on site inventory. Can you imagine the ;awsuit if that contract was usurp by a mook off the street. The on street customers are ours and not the vendors. If you want the prices and availability..Put 8 years into becoming a contractor. You forgot Contractors excise tax by the way. You can't pay that to the state each month without a license and you are now well into the quasi-felony stage. You chumps that squeak when you walk are fun to poke with sharp sticks.
Johnstones in Sioux Falls, SD, Appleton, Wisconsin, Fargo ND, and Sioux City Iowa all have large commercial signs on the front entrance that says Licensed and wholesale only. I assume those signs are nationwide and are enforced. There is also a minimum purchase price and only to account holders. Maybe your sister might be laying it out to a counterman that can get it for you?
Thats the countdown to self destruct. No Joke....
Dammit...Stop that. We aren't done playing with him yet.
There are excellent 2 year training programs at your local VoTech school that will get you accepted as an apprentice at graduation. I so hope you have good liability, health and fire insurance until then.
Try calling building Services at City Hall for a list of companies that have survived a lot of city and federal Job inspections. They certainly are not going to point you to a hack...If any should exist. I would suppose that your first question would be who can I get that will work at minimum wage or do you know any illegals that will do this?
Looks like that is near Chicago.. Heavy Union country. Be interesting to know who is superceding the service companies over there.
The relay is powered from the air handler via that skinny cable taped to the line set.
That's the kind of ignorance that gets people hurt. "but I thought...."