Is is ok (regs wise) to mount a Henley block upside down, or sidways on? ie So the cables can emerge in different directions. I have some 25mm^2 tails to change and it would be much easier if I could mount the HB at different angle (space constraints). thanks
electrical: orientation of Henley block
Nov 16, 2015
1 Replies
If you mount the Henley block upside down or horizontally then you need to meet IP4X.
formatting link
Silicone around the entry points or taking the cables through some trunking into the HB should suffice.
Cheers