CH/HW system is a Y-Plan design, Baxi Solo 40PF boiler.
Yesterday there was a hell of a racket coming from the boiler - a series of bangs maybe a second apart, a bit of wheezing etc., there's also sounds of bubbling through other parts of the pipe system. I'm not sure, but the boiler may cut out for a few minutes (I'm not sure of its characteristics before this started - I would have thought it'd be on continuous whilst there was a demand for heating the HW cylinder?)
My thoughts are that with the temperature dropping recently, the CH has kicked in, and disturbed the last 8 months of static water in the radiators, kicking up sediment, and presumably kicking this into the boiler clogging it up (heat exchanger?).
So, does the above make sense?, is this a likely scenario?
My thoughts to remedy this, bearing in mind the boiler is enclosed in a kitchen unit and the access to the pipework is, at best, minimal, is to drain the CH system down (via lowest radiator), probably leave the cold-feed on (F&E tank in loft) to do sort-of a low-pressure flush of the system.
I might also be tempted to fit one of those magnetic sludge removal devices (e.g. Fernox boiler buddy) to try to remove the suspended matter from the system
Does the above solution sound practical?, or is it (metaphorically speaking) pissing in the wind? If so, barring reaching for the yellow pages and my flexible friend, is there anything else I should be trying?
Regards
Mike