It would be very convenient for me to change my 45A cooker control unit for one with a 13A socket. Anyone know if this still allowed under the 17th edition?
Thanks, John
It would be very convenient for me to change my 45A cooker control unit for one with a 13A socket. Anyone know if this still allowed under the 17th edition?
Thanks, John
Yes it is allowed by the 17th but the circuit needs 30mA RCD protection.
Adam
Thanks for that Adam. John