I plan to bring power to my garage's sub-panel from a sub-panel at the pump house. The garage is situated on a rock built-up base/fill. My question is what is the burial requirements at the garage base/fill and at the flat area between the garage and the pump house. I understand that code is 18" with PVC. But that would be hard to do at the garage base/fill. Would Sch 80 PVC require less cover? Any suggestions. Thanks.
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
snipped-for-privacy@yahoo.com wrote:

If underground is difficult, have you considered going with an overhead line?
Chris
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
Galv pipe, 6" or cover the pvc with 2" concrete

Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload

You can use rigid galvanized pipe at 6" unless it goes under a driveway. In that case it would have to be 18".
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
Is there a permit involved? Or any other chance of do gooders intervention?