copper pipes and angle stops

Were having our bathroom repiped with copper pipe and my question is which type of angle stops should be used? The person sweating the pipes put in 1\2" female copper fittings then a galv. close nipple then the 1\2" female angle stop and they all seem to leak. would it not have been better to use a 1\2" compression angle stop on the copper pipe instead?
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
Galvinized fittings???? You have got to be kidding!
Get the compression angle stops. I have only had one fail in 25 years.
AZCRAIG

Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload

Copper and galv. pipe will eat away at each other. Basic chemistry. The galv. nipples MUST come out.
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
SQLit wrote:

The galv nipples ensure that the installer's son will have a job. Takes about 40 Years to disintegrate...
Jim
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
Dean Swinger wrote:

Are you sure it's a galvanized close nipple? If so, it sounds like the plumber didn't have the right parts at hand and used whatever he happened to have with him. Never mix copper and galvanized.
My personal favorite way is to have the female fitting behind the wall (either copper or brass), then connect a 3" or 4" chrome plated brass nipple, then either a straight stop or angle stop, whatever you need. Use teflon tape on all threaded fittings. Put on a chrome escutchion, and you're all set, looks real nice.
Ken
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
Dean Swinger wrote:

Are you sure it's a galvanized close nipple? If so, it sounds like the plumber didn't have the right parts at hand and used whatever he happened to have with him. Never mix copper and galvanized.
My personal favorite way is to have the female fitting behind the wall (either copper or brass), then connect a 3" or 4" chrome plated brass nipple, then either a straight stop or angle stop, whatever you need. Use teflon tape on all threaded fittings. Put on a chrome escutchion, and you're all set, looks real nice.
Ken
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
Thanks for the input thought it was odd to galv w/copper I removed the copper fitting and replaced it with a 3" long piece of 1\2" copper pipe and put a compression angle stop on it and it worked great. ! question though if you have a female fitting behiend the wall how do you tighten the angle stop without twisting the copper joint apart?

Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
Dean Swinger wrote:

Behind the wall I like to use a cast bronze elbow with the ears on it, like this:
http://tinyurl.com/cypty
That elbow is nailed to blocking between the studs. You can crank on a nipple of whatever length you need, then crank on a angle stop, should be no problem with twisting.
Ken
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload
Dean Swinger wrote:

1/2" compression, Period. Never had one fail. Hmmmmmmm copper and galv. two different metals in contact with eachother, bad news. Electrolysis!!!
Rich
--
*Remove "nospam" to email
"You can lead them to LINUX
  Click to see the full signature.
Add pictures here
<% if( /^image/.test(type) ){ %>
<% } %>
<%-name%>
Add image file
Upload

Site Timeline