I have a split Carrier unit (inside gas furnace/blower & outside compressor). The inside blower moter (2-speed) will not start as normal. I have elimated the thermostat (jumpered at the unit), it also appears the capacitor and motor are OK (I placed jumper from COM to both HI and LO connectors and the motor runs fine. That leaves the control board. The transformer seems OK (24V to 120V), but the relays do not seem to pull in. Any other steps I can take? Is it worth trying to troubleshoot down to the board level, or just replace? Any idea where I can acquire a board if needed? Thanks!!